Main Technical Parameters
Flexible selection of Auto/Manual modes;
Unique TOYI input signal filtering algorithm, effectively filtering spike signals hundreds of times the normal input range while maintaining a sampling speed of 8 samples/sec and technical indicator accuracy;
Multi-parameter display, simultaneously showing valve position measured value and setpoint value for convenient observation and debugging;
Equipped with functions such as simple valve position auto-calibration, electronic braking, frequent start prevention, and stall detection control;
Convenient positioning accuracy adjustment to ensure stable positioning and achieve "one-step" arrival functionality;
Programmable direct/reverse action and output upper and lower limit constraint functions.
2.Main Technical Indicators
Power Supply:100240VAC, less than 8W (Other voltages customizable)
Ambient Temperature:0-50℃, Humidity 3585%
Outline and Cutout Dimensions:Width×Height×Depth 96×96×110mm; Cutout:91+1×91+1mm
Display Range:0.0-100.0%
Display Accuracy:0.1%
Positioning Accuracy:Maximum positioning accuracy is ±0.1%
Acceptable Feedback Signal from Electric Actuator:Potentiometer:500Ω5KΩ; Current:4-20mA DC
Input:Standard Current/Voltage:420mA/15V DC (Other signals customizable), Input Impedance 250Ω
Output (With direct/reverse action selection and upper/lower limit functions):
1)Output relay contact capacity:250VAC, 3A
2)Valve opening feedback signal proportional analog output:420mA
Programmable Parameters:
1)Power-on state 2)Minimum set opening 3)Maximum set opening 4)Positioning accuracy 5)Signal input abnormality action or shielding
Calibratable Parameters:
1)Actuator range zero 2)Actuator range full 3)Input signal zero and span 4)Output signal zero and span
Note:Parameters are password protected; parameters 3 and 4 are reserved for factory use.